As regards a drying equipment and its attached equipment, the employer must carry out a self-inspection for the following matters periodically once every period not exceeding one year; provided, however, that this does not apply to the non-use period of a drying equipment and its attached equipment which is not used for a period exceeding one year:
事業者は、乾燥設備及びその附属設備については、一年以内ごとに一回、定期に、次の事項について自主検査を行なわなければならない。ただし、一年をこえる期間使用しない乾燥設備及びその附属設備の当該使用しない期間においては、この限りでない。
damage, deformation and corrosion both inside and outside of the equipment and shelves, frames, etc., inside;
内面及び外面並びに内部のたな、わく等の損傷、変形及び腐食の有無
for the drying equipment for dangerous goods, abnormalities in the equipment for discharging gas, vapor or dust generated from the drying operation that has the risk of explosion or fire;
危険物乾燥設備にあつては、乾燥に伴つて生ずるガス、蒸気又は粉じんで爆発又は火災の危険があるものを排出するための設備の異常の有無
for the drying equipment set forth in Article 294, item (vi), abnormalities in the equipment for ventilation of the combustion chamber or other places where materials are ignited;
第二百九十四条第六号の乾燥設備にあつては、燃焼室その他点火する箇所の換気のための設備の異常の有無
abnormalities in openings such as peep windows, manholes, and exhaust holes;
のぞき窓、出入口、排気孔等の開口部の異常の有無
abnormalities in devices for measuring and adjusting the inside temperature; and
内部の温度の測定装置及び調整装置の異常の有無
abnormalities in electric machine and appliance or wiring installed inside the equipment.
内部に設ける電気機械器具又は配線の異常の有無
As regards the drying equipment and its attached equipment set forth in the proviso of the preceding paragraph, the employer must carry out a self-inspection for the matters listed in each item of the same paragraph before resuming the use.
When having carried out the self-inspection set forth in the preceding two paragraphs, the employer must record the following matters and preserve the record for three years:
事業者は、前二項の自主検査を行つたときは、次の事項を記録し、これを三年間保存しなければならない。
the date of the inspection;
検査年月日
the method of the inspection;
検査方法
the parts inspected;
検査箇所
the results of the inspection;
検査の結果
the name of the person who has carried out the inspection; and
検査を実施した者の氏名
when measures such as repairs have been taken based on the result of the inspection, the details of the repairs.
検査の結果に基づいて補修等の措置を講じたときは、その内容
定義第二百八十条第一項
電動機、変圧器、コード接続器、開閉器、分電盤、配電盤等電気を通ずる機械、器具その他の設備のうち配線及び移動電線以外のもの
定義第二百八十七条第一項第四号
熱源を用いて火薬類取締法(昭和二十五年法律第百四十九号)第二条第一項に規定する火薬類以外の物を加熱乾燥する乾燥室及び乾燥器
わかりやすく言うと
熱源を使って物を加熱乾燥する乾燥室と乾燥器のことです。火薬類取締法でいう火薬類(火薬、爆薬、火工品)を乾燥するものは含みません。
略称規定第二百八十七条第一項第四号
乾燥設備(熱源を用いて火薬類取締法(昭和二十五年法律第百四十九号)第二条第一項に規定する火薬類以外の物を加熱乾燥する乾燥室及び乾燥器をいう。以下同じ。)で、危険物又は危険物が発生する乾燥物を加熱乾燥するもの(以下「危険物乾燥設備」という。…
わかりやすく言うと
熱源を使って物を加熱乾燥する乾燥室や乾燥器(火薬類を乾燥するものを除く)のうち、危険物や、危険物が発生する乾燥物を加熱乾燥するもののことです。