Article 263Handling of Gas Containers
As regards gas containers used for the work of gas welding, etc., (meaning the work listed in Article 20, item (x) of the Order; the same applies hereinafter) the employer must comply with the requirements set forth in the following items:
to not install, use, store or leave the gas containers in the following places:
次の場所においては、設置し、使用し、貯蔵し、又は放置しないこと。
places where there is insufficient airing or ventilation;
通風又は換気の不十分な場所
places where fires are used and their vicinities;
火気を使用する場所及びその附近
places where gun powder, dangerous goods, or other explosive or combustible substances or a large quantity of flammable substances are manufactured or handled and their vicinities;
火薬類、危険物その他の爆発性若しくは発火性の物又は多量の易燃性の物を製造し、又は取り扱う場所及びその附近
to keep the temperature of the containers at 40 degrees or lower;
容器の温度を四十度以下に保つこと。
to maintain the containers in such a way that they are not likely to fall;
転倒のおそれがないように保持すること。
to not give a shock to the containers;
衝撃を与えないこと。
to cap the containers when transporting them;
運搬するときは、キヤツプを施すこと。
to remove oil, etc., and dust adhering to the mouthpiece of the containers when using them;
使用するときは、容器の口金に付着している油類及びじんあいを除去すること。
to open and close the valve of the containers gently;
バルブの開閉は、静かに行なうこと。
to place a container for dissolved acetylene in an upright position; and
溶解アセチレンの容器は、立てて置くこと。
to clearly distinguish containers before use or in use from other containers.
使用前又は使用中の容器とこれら以外の容器との区別を明らかにしておくこと。
Article 264Prevention of Ignition Due to Contact with Different Types of Substances
When there is a risk of ignition or explosion due to contact with different types of substances, the employer must not store them close to each other, or load them on the same carrier; provided, however, this does not apply when measures to prevent the substances from coming into contact with each other are taken.
事業者は、異種の物が接触することにより発火し、又は爆発するおそれのあるときは、これらの物を接近して貯蔵し、又は同一の運搬機に積載してはならない。ただし、接触防止のための措置を講じたときは、この限りでない。
Article 265Workplace that Has a Risk of Fire
The employer must ensure that places, equipment, etc., where the work of nap raising, rag opening, etc., or work of handling a great quantity of cotton, wool, rags, excelsior, straw, wastepaper and other flammable substances, have appropriate location or structure to prevent fires.
事業者は、起毛、反毛等の作業又は綿、羊毛、ぼろ、木毛、わら、紙くずその他可燃性の物を多量に取り扱う作業を行なう場所、設備等については、火災防止のため適当な位置又は構造としなければならない。
Article 266Prevention of Spontaneous Combustion
When piling up substances that have the risk of spontaneous combustion, the employer must take measures to prevent the temperature of the substances from rising to a dangerous level.
事業者は、自然発火の危険がある物を積み重ねるときは、危険な温度に上昇しない措置を講じなければならない。
Article 267Disposal of Rags Soaked with Oil
As regards rags, wastepaper, etc., soaked with oil or printing ink, the employer must take measures for preventing fire, such as putting them in a non-combustible covered container.
事業者は、油又は印刷用インキ類によつて浸染したボロ、紙くず等については、不燃性の有がい容器に収める等火災防止のための措置を講じなければならない。
第三節 化学設備等
Section 3 Chemical Facilities
Article 268Buildings in Which Chemical Facilities Are Installed
As regards a building in which chemical facilities (excluding piping) are installed, the employer must use non-combustible materials to construct the walls, pillars, floors, girders, roofs, stairs, etc. (limited to those parts adjacent to the chemical facilities).
事業者は、化学設備(配管を除く。)を内部に設ける建築物については、当該建築物の壁、柱、床、はり、屋根、階段等(当該化学設備に近接する部分に限る。)を不燃性の材料で造らなければならない。
Article 269Prevention of Corrosion
As regards parts of chemical facilities (excluding valves or cocks) that come into contact with dangerous goods or substances with a flash point of 65 degrees or higher (hereinafter referred to as "dangerous goods, etc"), the employer must take measures such as constructing the parts with corrosion-resistant materials and providing linings, in accordance with the type, temperature or concentration, etc., of the dangerous goods, etc., in order to prevent explosions or fires due to extreme corrosion of the parts by the dangerous goods, etc.
Article 270Joining Parts of Cover Plates
As regards the joining parts of a cover plate, a flange, a valve, a cock, etc., of chemical facilities, the employer must take measures such as using gaskets to tightly attach the joint surfaces in order to prevent explosions or fires due to leakage of dangerous goods, etc., from the joining parts.
Article 271Indicating the Opening and Closing Direction of Valves
As regards the valves or cocks of chemical facilities or the switches, push buttons, etc., for operating the valves or cocks, the employer must take the following measures in order to prevent explosions or fires due to an operational error of the valves and cocks:
事業者は、化学設備のバルブ若しくはコック又はこれらを操作するためのスイッチ、押しボタン等については、これらの誤操作による爆発又は火災を防止するため、次の措置を講じなければならない。
to indicate the direction of opening and closing them; and
開閉の方向を表示すること。
to distinguish them by color, shape, etc.
色分け、形状の区分等を行うこと。
The measure under item (ii) of the preceding paragraph must not be distinction by color only.
前項第二号の措置は、色分けのみによるものであつてはならない。
Article 272Materials of Valves
The employer must conform to the following requirements for the valves or cocks of chemical facilities:
事業者は、化学設備のバルブ又はコックについては、次に定めるところによらなければならない。
to make the valves or cocks with durable materials in accordance with the frequency of opening and closing the valves or cocks, or the type, temperature, concentration, etc., of the dangerous goods, etc., pertaining to manufacturing or handling of chemicals; and
開閉のひん度及び製造又は取扱いに係る危険物等の種類、温度、濃度等に応じ、耐久性のある材料で造ること。
to provide double valves or cocks between the strainers, etc. that are frequently opened or removed during the use of chemical facilities and the nearest chemical facilities (excluding piping; hereinafter the same applies in this item); provided, however, that this does not apply when devices enabling confirmation that the valves or cocks between the strainers, etc., and the chemical facilities have been securely closed are provided.
化学設備の使用中にしばしば開放し、又は取り外すことのあるストレーナ等とこれらに最も近接した化学設備(配管を除く。以下この号において同じ。)との間には、二重に設けること。ただし、当該ストレーナ等と当該化学設備の間に設けられるバルブ又はコックが確実に閉止していることを確認することができる装置を設けるときは、この限りでない。
Article 273Indication of Types of Raw Materials Supplied
The employer must display, at a readily visible position, the type of raw materials, the facilities to which the raw materials are supplied and other necessary matters in order to prevent explosions or fires due to an error in supplying raw materials by workers who supply raw materials to chemical facilities (excluding piping).
事業者は、化学設備(配管を除く。)に原材料を送給する労働者が当該送給を誤ることによる爆発又は火災を防止するため、見やすい位置に、当該原材料の種類、当該送給の対象となる設備その他必要な事項を表示しなければならない。
Article 273-2Installing Measuring Instruments
As regards special chemical facilities, the employer must equip thermometers, flow meters, pressure gauges and other measuring instruments necessary to discover abnormal conditions in the facilities at an early stage.
事業者は、特殊化学設備については、その内部における異常な事態を早期には握するために必要な温度計、流量計、圧力計等の計測装置を設けなければならない。
Article 273-3Installation of an Automatic Warning Device
As regards special chemical facilities (excluding those facilities which manufacture or handle dangerous goods, etc., in a quantity less than the standard provided by the Minister of Health, Labour and Welfare), the employer must install an automatic warning device necessary to discover abnormal conditions in the facilities at an early stage.
When it is difficult to take the measures prescribed in the preceding paragraph, the employer must take measures such as placing a watcher and having the person monitor the special chemical facilities during operation.
Article 273-4Installation of an Emergency Stop Device
As regards special chemical facilities, the employer must install devices for coping with abnormal conditions, such as a device for cutting off feeding of raw materials or for discharging products, etc., and devices for feeding inert gas, cooling water, etc., in order to prevent explosions or fires due to abnormal conditions.
事業者は、特殊化学設備については、異常な事態の発生による爆発又は火災を防止するため、原材料の送給をしや断し、又は製品等を放出するための装置、不活性ガス、冷却用水等を送給するための装置等当該事態に対処するための装置を設けなければならない。
Valves or cocks to be equipped in the devices set forth in the preceding paragraph must conform to the requirements set forth in the following items:
前項の装置に設けるバルブ又はコツクについては、次に定めるところによらなければならない。
to have the function that reliably operates;
確実に作動する機能を有すること。
to maintain the valves or cocks in a condition that enables smooth operation at all times; and
常に円滑に作動できるような状態に保持すること。
to provide valves or cocks that enable safe and accurate operation.
安全かつ正確に操作することのできるものとすること。
Article 273-5Reserved Power Sources
The employer must conform to the requirements set forth in the following items regarding power sources used for special chemical facilities, their piping or their attached facilities:
事業者は、特殊化学設備、特殊化学設備の配管又は特殊化学設備の附属設備に使用する動力源については、次に定めるところによらなければならない。
to provide reserved power sources that enable immediate use, to prevent explosions or fires due to abnormalities of regular power sources; and
動力源の異常による爆発又は火災を防止するための直ちに使用することができる予備動力源を備えること。
to provide locking, distinction by color, sorting by shape, etc., on valves, cocks, switches, etc., in order to prevent operational errors.
バルブ、コツク、スイツチ等については、誤操作を防止するため、施錠、色分け、形状の区分等を行うこと。
The measures under item (ii) of the preceding paragraph must not be distinction by color only.
前項第二号の措置は、色分けのみによるものであつてはならない。
Article 274Work Rules
When carrying out the work using chemical facilities or their attached facilities, the employer must establish the rules for the facilities on the following matters to prevent explosions or fires, and have workers carry out work according to the rules:
事業者は、化学設備又はその附属設備を使用して作業を行うときは、これらの設備に関し、次の事項について、爆発又は火災を防止するため必要な規程を定め、これにより作業を行わせなければならない。
operation of valves, cocks, etc. (limited to those used to supply raw materials to or to take products out from chemical facilities (excluding piping; hereinafter the same applies in this item));
バルブ、コック等(化学設備(配管を除く。以下この号において同じ。)に原材料を送給し、又は化学設備から製品等を取り出す場合に用いられるものに限る。)の操作
operation of cooling devices, heating devices, stirring devices and compressors;
冷却装置、加熱装置、攪拌装置及び圧縮装置の操作
monitoring and adjustment of measuring instruments and the control device;
計測装置及び制御装置の監視及び調整
adjustment of safety devices such as safety valves and the emergency stop device and the automatic warning device;
安全弁、緊急しや断装置その他の安全装置及び自動警報装置の調整
inspection of joining parts of cover plates, flanges, valves, cocks, etc., for leakage of dangerous goods, etc.;
ふた板、フランジ、バルブ、コック等の接合部における危険物等の漏えいの有無の点検
collection of samples;
試料の採取
for special chemical facilities, work methods during the suspension of operation and at the time of the resumption of operation when operations are temporarily or partially suspended;
特殊化学設備にあつては、その運転が一時的又は部分的に中断された場合の運転中断中及び運転再開時における作業の方法
emergency measures in an abnormal situation; and
異常な事態が発生した場合における応急の措置
beyond what is set forth in the preceding items, necessary measures for preventing explosions or fires.
前各号に掲げるもののほか、爆発又は火災を防止するため必要な措置
Article 274-2Evacuation
If there is an imminent danger of the occurrence of an industrial injury due to explosion, fire, etc. of dangerous goods, etc., such as in the case where a large quantity of dangerous goods, etc. leaks from chemical facilities, the employer must immediately suspend the work and evacuate persons engaged in work to a safe place.
In the case referred to in the preceding paragraph, until it is confirmed that there is no risk of persons engaged in work suffering an industrial injury due to dangerous goods, etc., the employer must prohibit persons other than those concerned from entering the workshop, etc. by indicating the prohibition in a conspicuous place or by other methods, and, where the prohibition is made by a method other than indication, must indicate in a conspicuous place that the workshop, etc. is subject to the prohibition of entry.
Article 275Modifications and Repairs
In modifying, repairing or cleaning the chemical facilities or their attached facilities, the employer must conform to the requirements set forth in the following items when the work of disassembling the facilities are carried out or the work is carried out inside the facilities:
事業者は、化学設備又はその附属設備の改造、修理、清掃等を行う場合において、これらの設備を分解する作業を行い、又はこれらの設備の内部で作業を行うときは、次に定めるところによらなければならない。
to decide in advance the method and procedures of the work, and make them known to the workers concerned;
当該作業の方法及び順序を決定し、あらかじめ、これを関係労働者に周知させること。
to designate a supervisor of the work, and have the supervisor direct the work;
当該作業の指揮者を定め、その者に当該作業を指揮させること。
to doubly close the valves or cocks, or apply baffles to the valves or cocks as well as close them in order to prevent dangerous goods, etc. from leaking or high-temperature steam from being discharged inside the workplace;
作業箇所に危険物等が漏えいし、又は高温の水蒸気等が逸出しないように、バルブ若しくはコックを二重に閉止し、又はバルブ若しくはコックを閉止するとともに閉止板等を施すこと。
to lock the valves, cocks or baffles set forth in the preceding item and display a notice stating that the valves, cocks or baffles must not be opened, or placing a watcher; and
前号のバルブ、コック又は閉止板等に施錠し、これらを開放してはならない旨を表示し、又は監視人を置くこと。
in the case where the baffle, etc. set forth in item (iii) is to be removed and there is a risk of dangerous goods, etc., or high-temperature steam, etc. leaking or discharging, to take measures such as confirming in advance the presence or absence of dangerous goods, etc., or high-temperature steam, etc. between the baffle, etc. and the nearest valve or cock.
定義第四条第一項第三号
労働安全衛生法施行令(以下「令」という。)第九条の三第一号に掲げる化学設備
わかりやすく言うと
危険物(火薬類を除く)を製造し、若しくは取り扱う設備、又は引火点が六十五度以上の物を引火点以上の温度で製造し、若しくは取り扱う設備で、移動式でないもののことです。アセチレン溶接装置、ガス集合溶接装置、乾燥設備は除きます(施行令第九条の三第一号)。
略称規定第四条第一項第三号
…発熱反応が行われる反応器等異常化学反応又はこれに類する異常な事態により爆発、火災等を生ずるおそれのあるもの(配管を除く。以下「特殊化学設備」という。)を設置する事業場であつて…
わかりやすく言うと
化学設備(危険物などを製造し、又は取り扱う移動式以外の設備)のうち、発熱反応が行われる反応器など、異常な化学反応などにより爆発や火災などを生ずるおそれのあるもので、配管を除いたもののことです。
定義第三十条第一項第一号
令別表第一に掲げる危険物
わかりやすく言うと
労働安全衛生法施行令別表第一に掲げる、爆発性の物、発火性の物、酸化性の物、引火性の物、可燃性のガスのことです。
略称規定第二百六十二条第一項・この条及び第二百六十三条の中だけ
事業者は、通風又は換気が不十分な場所において、可燃性ガス及び酸素(以下この条及び次条において「ガス等」という。)を用いて溶接、溶断又は金属の加熱の作業を行なうときは、当該場所におけるガス等の漏えい又は放出による爆発…
わかりやすく言うと
可燃性ガスと酸素をまとめた呼び名で、この条と次の条で使われます。
定義第二百六十三条第一項
令第二十条第十号に掲げる業務
わかりやすく言うと
可燃性ガスと酸素を使って行う、金属の溶接、溶断又は加熱の業務のことです(労働安全衛生法施行令第二十条第十号)。
略称規定第二百六十九条第一項
事業者は、化学設備(バルブ又はコックを除く。)のうち危険物又は引火点が六十五度以上の物(以下「危険物等」という。)が接触する部分については、当該危険物等による当該部分の著しい腐食による爆発又は火災を防止するため、当該危険物等の種類、温度…
わかりやすく言うと
危険物(爆発性、発火性、酸化性、引火性の物や可燃性のガス)と、引火点が六十五度以上の物をまとめた呼び名です。