Article 649Measures Concerning Motor-Driven Appliances

第六百四十九条(電動機械器具についての措置)

In the case set forth in Article 31, paragraph (1) of the Act, when the orderer has persons engaged in work pertaining to the contractor use machines or equipment driven by motor (hereinafter referred to as "motor-driven appliance" in this Article) that are movable or portable with a voltage to ground exceeding 150 V, or that are movable or portable and used at places moistened with water or other liquids of high electric conduction or at places of high electric conduction such as on iron plates, steel frames and surface plates, the orderer must connect to the electrical circuit to which the motor-driven appliance is connected an earth-leakage circuit breaker for preventing electric shocks that complies with the rating of the electrical circuit, has good sensitivity and works reliably.

注文者は、法第三十一条第一項の場合において、請負人に係る作業従事者に電動機を有する機械又は器具(以下この条において「電動機械器具」という。)で、対地電圧が百五十ボルトを超える移動式若しくは可搬式のもの又は水等導電性の高い液体によつて湿潤している場所その他鉄板上、鉄骨上、定盤上等導電性の高い場所において使用する移動式若しくは可搬式のものを使用させるときは、当該電動機械器具が接続される電路に、当該電路の定格に適合し、感度が良好であり、かつ、確実に作動する感電防止用漏電しや断装置を接続しなければならない。

The orderer set forth in the preceding paragraph, when it is difficult to take the measures prescribed in the same paragraph, must ensure that the metallic portion of the outer frame of the motor-driven appliance or the cover of the motor is grounded pursuant to the provisions of each item of Article 333, paragraph (2).

前項の注文者は、同項に規定する措置を講ずることが困難なときは、電動機械器具の金属性外わく、電動機の金属製外被等の金属部分を、第三百三十三条第二項各号に定めるところにより接地できるものとしなければならない。

Read this with the articles around it

© 2026 japanlaw.orgA copy for reading and reference — not an official source, and not legal advice. Only the Japanese text published by the government has legal effect.Run by Genjido LLC (源氏道合同会社) · contact@genjido.comContactSourcesTermsPrivacy