When using electrical machinery and apparatus, etc. listed in the left column of the following table, the employer must, before commencing use for the day, inspect the inspection matters listed in the right column of the same table in accordance with the type of that electrical machinery and apparatus, etc., and when having found any abnormality, must immediately repair or replace it.
| Type of Electrical Machinery and Apparatus, etc. | Inspection Matters |
| Holders for welding rods, etc. set forth in Article 331 | Presence or absence of damage to the insulated protective portion and the connected portion of the cable for holders |
| Automatic voltage reducing devices for alternating current arc welding machines set forth in Article 332 | Operating state |
| Earth-leakage circuit breakers for preventing electric shock set forth in Article 333, paragraph (1) | |
| Motor-driven appliances set forth in Article 333 that are grounded by the method set forth in paragraph (2) of that Article | Presence or absence of abnormalities, such as disconnection of the ground wire or lifting of the grounding pole |
| Movable electric cables and the connecting tools attached to them set forth in Article 337 | Presence or absence of damage to the covering or sheathing |
| Voltage detectors set forth in Article 339, paragraph (1), item (iii) | Voltage detection performance |
| Short-circuit grounding equipment set forth in Article 339, paragraph (1), item (iii) | Presence or absence of damage to the mounting fittings and grounding lead wires |
| Insulating protective equipment set forth in Articles 341 through 343 | Presence or absence of damage such as cracks, splits and tears, and dryness |
| Insulating devices set forth in Articles 341 and 342 | |
| Live line work equipment set forth in Article 341 and Articles 343 through 345 | |
| Live line work instruments set forth in Articles 341, 343 and 344 | |
| Insulating protective equipment and live line work instruments set forth in Articles 346 and 347, and insulating devices set forth in Article 347 | |
| Insulating protective devices set forth in Article 349, item (iii) and Article 570, paragraph (1), item (vi) |
事業者は、次の表の上欄に掲げる電気機械器具等を使用するときは、その日の使用を開始する前に当該電気機械器具等の種別に応じ、それぞれ同表の下欄に掲げる点検事項について点検し、異常を認めたときは、直ちに、補修し、又は取り換えなければならない。
| 電気機械器具等の種別 | 点検事項 |
| 第三百三十一条の溶接棒等のホルダー | 絶縁防護部分及びホルダー用ケーブルの接続部の損傷の有無 |
| 第三百三十二条の交流アーク溶接機用自動電撃防止装置 | 作動状態 |
| 第三百三十三条第一項の感電防止用漏電しや断装置 | |
| 第三百三十三条の電動機械器具で、同条第二項に定める方法により接地をしたもの | 接地線の切断、接地極の浮上がり等の異常の有無 |
| 第三百三十七条の移動電線及びこれに附属する接続器具 | 被覆又は外装の損傷の有無 |
| 第三百三十九条第一項第三号の検電器具 | 検電性能 |
| 第三百三十九条第一項第三号の短絡接地器具 | 取付金具及び接地導線の損傷の有無 |
| 第三百四十一条から第三百四十三条までの絶縁用保護具 | ひび、割れ、破れその他の損傷の有無及び乾燥状態 |
| 第三百四十一条及び第三百四十二条の絶縁用防具 | |
| 第三百四十一条及び第三百四十三条から第三百四十五条までの活線作業用装置 | |
| 第三百四十一条、第三百四十三条及び第三百四十四条の活線作業用器具 | |
| 第三百四十六条及び第三百四十七条の絶縁用保護具及び活線作業用器具並びに第三百四十七条の絶縁用防具 | |
| 第三百四十九条第三号及び第五百七十条第一項第六号の絶縁用防護具 |
Read this with the articles around it
electrical machinery and apparatusmachine translation
「電気機械器具」
Equipment that carries electricity, such as motors, transformers, cord connectors, switches, distribution boards and switchboards, other than wiring and movable electric wires.
Defined inArticle 280, paragraph (1)
motor-driven appliance
「電動機械器具」
A machine or appliance with an electric motor.
Short name set inArticle 333, paragraph (1)