As regards chemical facilities (excluding piping; hereinafter the same applies in this Article) and their attached facilities, the employer must carry out a self-inspection for the following matters periodically once every period not exceeding two years; provided, however, that this does not apply to the non-use period of chemical facilities and their attached facilities which are not used for a period exceeding two years:
事業者は、化学設備(配管を除く。以下この条において同じ。)及びその附属設備については、二年以内ごとに一回、定期に、次の事項について自主検査を行わなければならない。ただし、二年を超える期間使用しない化学設備及びその附属設備の当該使用しない期間においては、この限りでない。
existence of the substances inside the facilities that may cause explosions or fires;
爆発又は火災の原因となるおそれのある物の内部における有無
existence of marked damage, deformation or corrosion on internal and external surfaces of the facilities;
内面及び外面の著しい損傷、変形及び腐食の有無
condition of cover plates, flanges, valves, cocks, etc.;
ふた板、フランジ、バルブ、コック等の状態
functions of safety devices, such as safety valves and emergency stops, and of automatic warning devices;
安全弁、緊急しや断装置その他の安全装置及び自動警報装置の機能
functions of cooling devices, heating devices, stirring devices, compressors, measuring instruments and the control device;
冷却装置、加熱装置、攪拌装置、圧縮装置、計測装置及び制御装置の機能
functions of reserve power sources; and
予備動力源の機能
beyond what is set forth in the preceding items, matters especially necessary for preventing explosions or fires.
前各号に掲げるもののほか、爆発又は火災を防止するため特に必要な事項
As regards the chemical facilities and their attached facilities set forth in the proviso of the preceding paragraph, the employer must carry out a self-inspection for the matters listed in each item of the same paragraph before resuming the use.
When having found an abnormality in the chemical facilities and their attached facilities as a result of the self-inspection set forth in the preceding two paragraphs, the employer must not use the facilities unless having made repairs or taken other necessary measures.
When having carried out the self-inspection set forth in paragraph (1) and (2), the employer must record the following matters and preserve the record for three years:
the date of the inspection;
検査年月日
the method of the inspection;
検査方法
the parts inspected;
検査箇所
the results of the inspection;
検査の結果
the name of the person who has carried out the inspection; and
検査を実施した者の氏名
when measures such as repairs have been taken based on the result of the inspection, the details of the repairs.
検査の結果に基づいて補修等の措置を講じたときは、その内容
Read this with the articles around it
chemical facilities
「化学設備」
Fixed (not mobile) equipment that makes or handles dangerous goods, or makes or handles substances with a flash point of 65 degrees Celsius or higher at or above that flash point, other than acetylene welding equipment, gas welding equipment using manifolds and drying equipment, as Article 9-3, item (i) of the Order for Enforcement of Industrial Safety and Health Act defines it.
Defined inArticle 4, paragraph (1), item (iii)