When opening a switch such as a disconnector and line switch for high voltage or extra-high voltage electrical circuit that is not for breaking the load current, the employer must have the workers engaged in the operation confirm that the electric circuit is at no load using a pilot lamp for indicating that the electric circuit is at no load, a tablet for identifying the electrical circuit, etc.; provided, however, that this does not apply when a locking device is provided for the switch that does not allow the circuit to open unless the electrical circuit is at no load.
Read this with the articles around it
extra-high voltagemachine translation
「特別高圧」
Electrical voltage above 7,000 volts.
Defined inArticle 36, paragraph (1), item (iv)
high voltagemachine translation
「高圧」
Electrical voltage above 750 volts for direct current, or above 600 volts for alternating current, up to 7,000 volts.
Defined inArticle 36, paragraph (1), item (iv)