When carrying out electric work such as installation, inspection, repairing or painting of an electrical circuit or its support while opening the electrical circuit, the employer must take the following measures for the electrical circuit after opening the electrical circuit. This also applies to the case of carrying out an electric work such as installation, inspection, repairing or painting of an electrical circuit or its support in proximity to the electrical circuit or work such as the construction, dismantling, inspection, repairing or painting of a structure in proximity to the electrical circuit (excluding the support of an electrical circuit; hereinafter the same applies in this Chapter):
事業者は、電路を開路して、当該電路又はその支持物の敷設、点検、修理、塗装等の電気工事の作業を行なうときは、当該電路を開路した後に、当該電路について、次に定める措置を講じなければならない。当該電路に近接する電路若しくはその支持物の敷設、点検、修理、塗装等の電気工事の作業又は当該電路に近接する工作物(電路の支持物を除く。以下この章において同じ。)の建設、解体、点検、修理、塗装等の作業を行なう場合も同様とする。
to lock the switch used for circuit opening during work, or indicate necessary matters on prohibition of electric charge, or place a watcher;
開路に用いた開閉器に、作業中、施錠し、若しくは通電禁止に関する所要事項を表示し、又は監視人を置くこと。
as regards the opened circuit that are equipped with a power cable, power capacitor, etc., and have a risk of danger due to residual electric charge, to completely discharge the residual charge by a safe method; and
開路した電路が電力ケーブル、電力コンデンサー等を有する電路で、残留電荷による危険を生ずるおそれのあるものについては、安全な方法により当該残留電荷を確実に放電させること。
as regards the opened circuit that is of high voltage or extra-high voltage, to confirm the power cut with voltage detector, and short circuit to ground securely with a short circuit grounding equipment to prevent the danger of electric shocks due to erroneous turning on the electricity, confusion with other circuits, or induction from other circuits.
When seeking to turn on the electricity on the opened circuit during work set forth in the preceding paragraph or when the work is finished, the employer must not turn on the electricity unless having confirmed that it is not likely to cause danger of electric shocks to the worker engaging in the work and that the short circuit grounding equipment has been removed in advance.
事業者は、前項の作業中又は作業を終了した場合において、開路した電路に通電しようとするときは、あらかじめ、当該作業に従事する労働者について感電の危険が生ずるおそれのないこと及び短絡接地器具を取りはずしたことを確認した後でなければ、行なつてはならない。
Read this with the articles around it
extra-high voltagemachine translation
「特別高圧」
Electrical voltage above 7,000 volts.
Defined inArticle 36, paragraph (1), item (iv)
high voltagemachine translation
「高圧」
Electrical voltage above 750 volts for direct current, or above 600 volts for alternating current, up to 7,000 volts.
Defined inArticle 36, paragraph (1), item (iv)