When using electrical machinery and apparatus, etc. listed in the left column of the following table, the employer must, before commencing use for the day, inspect the inspection matters listed in the right column of the same table in accordance with the type of that electrical machinery and apparatus, etc., and when having found any abnormality, must immediately repair or replace it.
| Type of Electrical Machinery and Apparatus, etc. | Inspection Matters |
| Holders for welding rods, etc. set forth in Article 331 | Presence or absence of damage to the insulated protective portion and the connected portion of the cable for holders |
| Automatic voltage reducing devices for alternating current arc welding machines set forth in Article 332 | Operating state |
| Earth-leakage circuit breakers for preventing electric shock set forth in Article 333, paragraph (1) |
| Motor-driven appliances set forth in Article 333 that are grounded by the method set forth in paragraph (2) of that Article | Presence or absence of abnormalities, such as disconnection of the ground wire or lifting of the grounding pole |
| Movable electric cables and the connecting tools attached to them set forth in Article 337 | Presence or absence of damage to the covering or sheathing |
| Voltage detectors set forth in Article 339, paragraph (1), item (iii) | Voltage detection performance |
| Short-circuit grounding equipment set forth in Article 339, paragraph (1), item (iii) | Presence or absence of damage to the mounting fittings and grounding lead wires |
| Insulating protective equipment set forth in Articles 341 through 343 | Presence or absence of damage such as cracks, splits and tears, and dryness |
| Insulating devices set forth in Articles 341 and 342 |
| Live line work equipment set forth in Article 341 and Articles 343 through 345 |
| Live line work instruments set forth in Articles 341, 343 and 344 |
| Insulating protective equipment and live line work instruments set forth in Articles 346 and 347, and insulating devices set forth in Article 347 |
| Insulating protective devices set forth in Article 349, item (iii) and Article 570, paragraph (1), item (vi) |