Search

Search provisions, jump to a law or an article

This text is not in force yetIt on 1 April 2027, in 4 months

Read the text in force →

Ordinance on Industrial Safety and Health

労働安全衛生規則(ろうどうあんぜんえいせいきそく)

Chapter III Air Volume and Ventilation

The law as Ministerial Order Partially Amending the Ordinance on Industrial Safety and Health (Ministry of Health, Labour and Welfare Order No. 112 of 2026) leaves it, with the words it changes marked.

The main text is read a page at a time: a chapter to a page, and a long chapter in runs of articles. The whole main text, and the supplementary provisions and appended tables this amendment changes. Those it leaves untouched are on the page for the text in force.

How the changes are shown

Underlined: words the amendment adds. A bar: where it removes words.Underlined: words the amendment adds. Struck through: the words it removes.Underlined: words the amendment adds. Struck through: the words it removes.

Chapter III Air Volume and Ventilation第三章 気積及び換気

Article 600第六百条

Air Volume(気積)
Article 600, paragraph (1)

The employer must ensure that the air volume per worker at an indoor workshop where workers are regularly engaged in work is 10 m3 or more, excluding the capacity occupied by the facilities and the space that exceeds 4 m in height from the floor surface.

事業者は、労働者を常時就業させる屋内作業場の気積を、設備の占める容積及び床面から四メートルをこえる高さにある空間を除き、労働者一人について、十立方メートル以上としなければならない。

Article 601第六百一条

Ventilation(換気)
Article 601, paragraph (1)

In an indoor workshop where workers are regularly engaged in work, the employer must ensure that the total area for the part where the windows and other openings can be opened directly to the open air is one-twentieth or more of the floor area at all times; provided, however, that this does not apply when the indoor workshop is provided with facilities capable of providing sufficient ventilation.

事業者は、労働者を常時就業させる屋内作業場においては、窓その他の開口部の直接外気に向つて開放することができる部分の面積が、常時床面積の二十分の一以上になるようにしなければならない。ただし、換気が十分行なわれる性能を有する設備を設けたときは、この限りでない。

Article 601, paragraph (2)

When the atmospheric temperature of the indoor workshop in the preceding Article is 10 degrees or lower, the employer must ensure that workers are not exposed to an air current of 1 m/sec or more in the process of ventilation.

事業者は、前条の屋内作業場の気温が十度以下であるときは、換気に際し、労働者を毎秒一メートル以上の気流にさらしてはならない。

Article 602第六百二条

Ventilation System in a Pit(坑内の通気設備)
Article 602, paragraph (1)

The employer must provide a workshop in a pit with a ventilation system in order to supply enough air to the workshop for health purposes; provided, however, that this does not apply to the workshop where sufficient air for health purposes is supplied by natural ventilation.

事業者は、坑内の作業場においては、衛生上必要な分量の空気を坑内に送給するために、通気設備を設けなければならない。ただし、自然換気により衛生上必要な分量の空気が供給される坑内の作業場については、この限りでない。

Article 603第六百三条

Measurement of Ventilation Volume in a Pit(坑内の通気量の測定)
Article 603, paragraph (1)

As regards a workshop in a pit set forth in Article 589, item (iii), the employer must measure the ventilation volume in the workshop, periodically once every period not exceeding half a month.

事業者は、第五百八十九条第三号の坑内の作業場について、半月以内ごとに一回、定期に、当該作業場における通気量を測定しなければならない。

Article 603, paragraph (2)

The provisions of Article 590, paragraph (2) apply mutatis mutandis to the cases measurements pursuant to the provisions of the preceding paragraph have been carried out.

第五百九十条第二項の規定は、前項の規定による測定を行つた場合について準用する。