Search

Search provisions, jump to a law or an article

This text is not in force yetIt on 1 April 2027, in 4 months

Read the text in force →

Ordinance on Industrial Safety and Health

労働安全衛生規則(ろうどうあんぜんえいせいきそく)

Chapter IV Prevention of Explosions and Fires (Articles 275-2 to 287)

The law as Ministerial Order Partially Amending the Ordinance on Industrial Safety and Health, etc. (Ministry of Health, Labour and Welfare Order No. 89 of 2026) leaves it, with the words it changes marked.

The main text is read a page at a time: a chapter to a page, and a long chapter in runs of articles. The whole main text, and the supplementary provisions and appended tables this amendment changes. Those it leaves untouched are on the page for the text in force.

How the changes are shown

Underlined: words the amendment adds. A bar: where it removes words.Underlined: words the amendment adds. Struck through: the words it removes.Underlined: words the amendment adds. Struck through: the words it removes.

Article 275-2第二百七十五条の二

Article 275-2, paragraph (1)

When carrying out the work set forth in the preceding Article, the employer must measure the concentration of the vapor of inflammable substances or the combustible gas at the workplace and its surrounding, as needed.

事業者は、前条の作業を行うときは、随時、作業箇所及びその周辺における引火性の物の蒸気又は可燃性ガスの濃度を測定しなければならない。

Article 276第二百七十六条

Periodical Self-inspection(定期自主検査)
Article 276, paragraph (1)

As regards chemical facilities (excluding piping; hereinafter the same applies in this Article) and their attached facilities, the employer must carry out a self-inspection for the following matters periodically once every period not exceeding two years; provided, however, that this does not apply to the non-use period of chemical facilities and their attached facilities which are not used for a period exceeding two years:

事業者は、化学設備(配管を除く。以下この条において同じ。)及びその附属設備については、二年以内ごとに一回、定期に、次の事項について自主検査を行わなければならない。ただし、二年を超える期間使用しない化学設備及びその附属設備の当該使用しない期間においては、この限りでない。

Article 276, paragraph (1), item (i)

existence of the substances inside the facilities that may cause explosions or fires;

爆発又は火災の原因となるおそれのある物の内部における有無

Article 276, paragraph (1), item (ii)

existence of marked damage, deformation or corrosion on internal and external surfaces of the facilities;

内面及び外面の著しい損傷、変形及び腐食の有無

Article 276, paragraph (1), item (iii)

condition of cover plates, flanges, valves, cocks, etc.;

ふた板、フランジ、バルブ、コック等の状態

Article 276, paragraph (1), item (iv)

functions of safety devices, such as safety valves and emergency stops, and of automatic warning devices;

安全弁、緊急しや断装置その他の安全装置及び自動警報装置の機能

Article 276, paragraph (1), item (v)

functions of cooling devices, heating devices, stirring devices, compressors, measuring instruments and the control device;

冷却装置、加熱装置、攪拌装置、圧縮装置、計測装置及び制御装置の機能

Article 276, paragraph (1), item (vi)

functions of reserve power sources; and

予備動力源の機能

Article 276, paragraph (1), item (vii)

beyond what is set forth in the preceding items, matters especially necessary for preventing explosions or fires.

前各号に掲げるもののほか、爆発又は火災を防止するため特に必要な事項

Article 276, paragraph (2)

As regards the chemical facilities and their attached facilities set forth in the proviso of the preceding paragraph, the employer must carry out a self-inspection for the matters listed in each item of the same paragraph before resuming the use.

事業者は、前項ただし書の化学設備及びその附属設備については、その使用を再び開始する際に、同項各号に掲げる事項について自主検査を行なわなければならない。

Article 276, paragraph (3)

When having found an abnormality in the chemical facilities and their attached facilities as a result of the self-inspection set forth in the preceding two paragraphs, the employer must not use the facilities unless having made repairs or taken other necessary measures.

事業者は、前二項の自主検査の結果、当該化学設備又はその附属設備に異常を認めたときは、補修その他必要な措置を講じた後でなければ、これらの設備を使用してはならない。

Article 276, paragraph (4)

When having carried out the self-inspection set forth in paragraph (1) and (2), the employer must record the following matters and preserve the record for three years:

事業者は、第一項又は第二項の自主検査を行つたときは、次の事項を記録し、これを三年間保存しなければならない。

Article 276, paragraph (4), item (i)

the date of the inspection;

検査年月日

Article 276, paragraph (4), item (ii)

the method of the inspection;

検査方法

Article 276, paragraph (4), item (iii)

the parts inspected;

検査箇所

Article 276, paragraph (4), item (iv)

the results of the inspection;

検査の結果

Article 276, paragraph (4), item (v)

the name of the person who has carried out the inspection; and

検査を実施した者の氏名

Article 276, paragraph (4), item (vi)

when measures such as repairs have been taken based on the result of the inspection, the details of the repairs.

検査の結果に基づいて補修等の措置を講じたときは、その内容

Article 276, paragraph (5)

The provisions of paragraph (1), paragraph (2) and the preceding paragraph apply mutatis mutandis to the self-inspection pursuant to the provisions of Article 45, paragraph (2) of the Act. In this case, the term "employer" in these provisions is deemed to be replaced with "individual business operator."

第一項、第二項及び前項の規定は、法第四十五条第二項の規定による自主検査について準用する。この場合において、これらの規定中「事業者」とあるのは「個人事業者」と読み替えるものとする。

Article 276, paragraph (6)

When having found an abnormality in the chemical facilities or their attached equipment as a result of the self-inspection set forth in paragraph (1) or (2) as applied mutatis mutandis pursuant to the preceding paragraph, the individual business operator is to use these facilities after repairs have been made or other necessary measures have been taken.

個人事業者は、前項において準用する第一項又は第二項の自主検査の結果、当該化学設備又はその附属設備に異常を認めたときは、補修その他必要な措置を講じた後に、これらの設備を使用するものとする。

Article 277第二百七十七条

Inspection before Commencing Use(使用開始時の点検)
Article 277, paragraph (1)

When using chemical facilities (excluding piping; hereinafter the same applies in this Article) or their attached facilities for the first time, after having dismantled and remodeled or repaired them, or after a non-use period of one month or longer, the employer must not use the facilities unless they have confirmed that there is no abnormality by carrying out the inspection on the matters listed in each item of paragraph (1) of the preceding Article.

事業者は、化学設備(配管を除く。以下この条において同じ。)又はその附属設備を初めて使用するとき、分解して改造若しくは修理を行つたとき、又は引き続き一月以上使用しなかつたときは、これらの設備について前条第一項各号に掲げる事項を点検し、異常がないことを確認した後でなければ、これらの設備を使用してはならない。

Article 277, paragraph (2)

In addition to the case referred to in the preceding paragraph, when changing the use of chemical facilities or their attached facilities (including changing the type of raw materials used; hereinafter the same applies in this paragraph), the employer must not use the facilities unless they have confirmed that there is no abnormality by inspecting the facilities for the matters listed in paragraph (1), item (i), item (iv) and item (v) of the preceding Article and the parts modified for the changes in use.

事業者は、前項の場合のほか、化学設備又はその附属設備の用途の変更(使用する原材料の種類を変更する場合を含む。以下この項において同じ。)を行なうときは、前条第一項第一号、第四号及び第五号に掲げる事項並びにその用途の変更のために改造した部分の異常の有無を点検し、異常がないことを確認した後でなければ、これらの設備を使用してはならない。

Article 278第二百七十八条

Safety Device(安全装置)
Article 278, paragraph (1)

As regards containers in which the pressure of gas is likely to exceed the atmospheric pressure due to an abnormal chemical reaction or other abnormal conditions, the employer must not use them unless they are provided with a safety valve or other alternative safety devices; provided, however, that this does not apply to the containers having a volume of 0.1 m3 or less.

事業者は、異常化学反応その他の異常な事態により内部の気体の圧力が大気圧を超えるおそれのある容器については、安全弁又はこれに代わる安全装置を備えているものでなければ、使用してはならない。ただし、内容積が〇・一立方メートル以下である容器については、この限りでない。

Article 278, paragraph (2)

As regards a safety valve or alternative safety device for the containers set forth in the preceding paragraph, in order to prevent explosions or fires due to dangerous goods (if the containers set forth in the preceding paragraph are chemical facilities (excluding piping) that manufacture or handle substances having a flash point of 65 degrees or higher at the temperature equal to or higher than the flash point, the substances; hereinafter the same applies in this paragraph) discharged by the operation of the safety valve or alternative safety device, the employer must use the safety valve or alternative safety device having an airtight structure, or one with the structure that enables discharged dangerous goods to be conveyed to a safe place or to be safely disposed by burning, absorbing, etc.

事業者は、前項の容器の安全弁又はこれに代わる安全装置については、その作動に伴つて排出される危険物(前項の容器が引火点が六十五度以上の物を引火点以上の温度で製造し、又は取り扱う化学設備(配管を除く。)である場合にあつては、当該物。以下この項において同じ。)による爆発又は火災を防止するため、密閉式の構造のものとし、又は排出される危険物を安全な場所へ導き、若しくは燃焼、吸収等により安全に処理することができる構造のものとしなければならない。

Section 4 Control of Fires第四節 火気等の管理

Article 279第二百七十九条

Prohibition of Use of Fire at Places Where Dangerous Goods Exist(危険物等がある場所における火気等の使用禁止)
Article 279, paragraph (1)

The employer must not use machinery or other such equipment, or fires that produce sparks or arcs, or that reach a high temperature and are liable to become an ignition source at places where there is a risk of explosion or fire due to the existence of combustible dust other than dangerous goods, gunpowder, a large quantity of easily flammable substances or dangerous goods.

事業者は、危険物以外の可燃性の粉じん、火薬類、多量の易燃性の物又は危険物が存在して爆発又は火災が生ずるおそれのある場所においては、火花若しくはアークを発し、若しくは高温となつて点火源となるおそれのある機械等又は火気を使用してはならない。

Article 279, paragraph (2)

A person engaged in work at the place set forth in the preceding paragraph must not use, at that place, machinery or other such equipment, or fire, that has the risk of becoming an ignition source set forth in that paragraph.

前項の場所において作業に従事する者は、当該場所においては、同項の点火源となるおそれのある機械等又は火気を使用してはならない。

Article 280第二百八十条

Electric Machine and Appliance Used in Places that Have a Risk of Explosion(爆発の危険のある場所で使用する電気機械器具)
Article 280, paragraph (1)

When using electrical machinery and apparatus (meaning those, among machines, instruments and other equipment that conduct electricity such as a motor, transformer, cord connector, switch, distribution board or switchboard, other than wiring and movable electric cables; the same applies hereinafter) at a place, among the places set forth in Article 261, where the vapor of an inflammable substance or combustible gas is still liable to reach a concentration at which there is a danger of explosion even after the measures set forth in that Article are taken, the employer must not use them unless they are explosion-proof electrical machinery and apparatus that have explosion-proof performance in accordance with the type of the vapor or gas and the likelihood of its reaching a concentration at which there is a danger of explosion.

事業者は、第二百六十一条の場所のうち、同条の措置を講じても、なお、引火性の物の蒸気又は可燃性ガスが爆発の危険のある濃度に達するおそれのある箇所において電気機械器具(電動機、変圧器、コード接続器、開閉器、分電盤、配電盤等電気を通ずる機械、器具その他の設備のうち配線及び移動電線以外のものをいう。以下同じ。)を使用するときは、当該蒸気又はガスに対しその種類及び爆発の危険のある濃度に達するおそれに応じた防爆性能を有する防爆構造電気機械器具でなければ、使用してはならない。

Article 280, paragraph (2)

A worker must not use electric machines and appliances other than the explosion-proof electric machines and appliances set forth in the preceding paragraph at places set forth in the same paragraph.

労働者は、前項の箇所においては、同項の防爆構造電気機械器具以外の電気機械器具を使用してはならない。

Article 281第二百八十一条

Article 281, paragraph (1)

As regards places set forth in Article 261, when using an electric machine and appliance at a place where flammable dust (excluding deflagration dust such as the dust of magnesium and aluminum) is liable to reach the explosive concentration even after the measures set forth in the same Article have been taken, the employer may not use electric machine and appliance unless it is an explosion-proof electric machine and appliance that has explosion-proof function for the dust.

事業者は、第二百六十一条の場所のうち、同条の措置を講じても、なお、可燃性の粉じん(マグネシウム粉、アルミニウム粉等爆燃性の粉じんを除く。)が爆発の危険のある濃度に達するおそれのある箇所において電気機械器具を使用するときは、当該粉じんに対し防爆性能を有する防爆構造電気機械器具でなければ、使用してはならない。

Article 281, paragraph (2)

A worker must not use an electric machine and appliance other than the explosion-proof electric machine and appliance set forth in the preceding paragraph at places set forth in the same paragraph.

労働者は、前項の箇所においては、同項の防爆構造電気機械器具以外の電気機械器具を使用してはならない。

Article 282第二百八十二条

Article 282, paragraph (1)

When using an electric machine and appliance at places where there is a risk of explosion due to existing deflagration dust, the employer must not use the electric machine and appliance unless it is an explosion-proof electric machine and appliance that has an explosion-proof function for the dust.

事業者は、爆燃性の粉じんが存在して爆発の危険のある場所において電気機械器具を使用するときは、当該粉じんに対して防爆性能を有する防爆構造電気機械器具でなければ、使用してはならない。

Article 282, paragraph (2)

A worker must not use an electric machine and appliance other than the explosion-proof electric machine and appliance set forth in the preceding paragraph at places set forth in the same paragraph.

労働者は、前項の場所においては、同項の防爆構造電気機械器具以外の電気機械器具を使用してはならない。

Article 283第二百八十三条

Exclusion from Application for Repair Work(修理作業等の適用除外)
Article 283, paragraph (1)

The provisions of the preceding four Articles do not apply to the case of carrying out temporary work such as repairs or alterations, and taking measures which are not likely to cause explosion or fire.

前四条の規定は、修理、変更等臨時の作業を行なう場合において、爆発又は火災の危険が生ずるおそれのない措置を講ずるときは適用しない。

Article 284第二百八十四条

Inspection(点検)
Article 284, paragraph (1)

When using an explosion-proof electric machine and appliance set forth in Articles 280 through 282 (limited to movable or portable types) pursuant to the provisions of those Articles, the employer must inspect the explosion-proof electric machine and appliance, and the condition of the outer part of the movable electric cable connected to the machine and the connecting part of the machine and the cable before commencing the use for the day, and when having found any abnormality, immediately make repairs.

事業者は、第二百八十条から第二百八十二条までの規定により、当該各条の防爆構造電気機械器具(移動式又は可搬式のものに限る。)を使用するときは、その日の使用を開始する前に、当該防爆構造電気機械器具及びこれに接続する移動電線の外装並びに当該防爆構造電気機械器具と当該移動電線との接続部の状態を点検し、異常を認めたときは、直ちに補修しなければならない。

Article 285第二百八十五条

Welding of Piping or a Container with Residual Oil(油類等の存在する配管又は容器の溶接等)
Article 285, paragraph (1)

As regards piping or a tank, a drum or other containers in which inflammable oil or combustible dust other than dangerous goods, or dangerous goods are likely to exist, the employer must not have a worker carry out welding, fusing or other work using fire, or work that is likely to produce sparks unless measures for preventing explosions or fires, such as removing, etc., the inflammable oil or combustible dust other than the dangerous goods, or dangerous goods have been taken in advance.

事業者は、危険物以外の引火性の油類若しくは可燃性の粉じん又は危険物が存在するおそれのある配管又はタンク、ドラムかん等の容器については、あらかじめ、これらの危険物以外の引火性の油類若しくは可燃性の粉じん又は危険物を除去する等爆発又は火災の防止のための措置を講じた後でなければ、溶接、溶断その他火気を使用する作業又は火花を発するおそれのある作業をさせてはならない。

Article 285, paragraph (2)

A worker must not carry out the work set forth in the preceding paragraph until the measures set forth in the same paragraph have been taken.

労働者は、前項の措置が講じられた後でなければ、同項の作業をしてはならない。

Article 286第二百八十六条

Welding at Places Where Ventilation Is Insufficient(通風等の不十分な場所での溶接等)
Article 286, paragraph (1)

When carrying out the work of welding, fusing, heating metal or other work using fire, or dry grinding using grinding wheels, chipping using a chisel or other work that is likely to produce sparks at a place where ventilation is insufficient, the employer must not use oxygen for the purpose of airing or ventilation.

事業者は、通風又は換気が不十分な場所において、溶接、溶断、金属の加熱その他火気を使用する作業又は研削といしによる乾式研ま、たがねによるはつりその他火花を発するおそれのある作業を行なうときは、酸素を通風又は換気のために使用してはならない。

Article 286, paragraph (2)

A worker must not use oxygen for the purpose of airing or ventilation in the case referred to in the preceding paragraph.

労働者は、前項の場合には、酸素を通風又は換気のために使用してはならない。

Article 286-2第二百八十六条の二

Anti-Static Work Clothes(静電気帯電防止作業服等)
Article 286-2, paragraph (1)

When carrying out the work at the locations set forth in Article 280 and Article 281 and the places set forth in Article 282, the employer must take measures to eliminate static electricity from the bodies and work clothes, etc., of workers, such as ensuring that the worker engaging in the work wear anti-static work clothes and anti-static work shoes.

事業者は、第二百八十条及び第二百八十一条の箇所並びに第二百八十二条の場所において作業を行うときは、当該作業に従事する労働者に静電気帯電防止作業服及び静電気帯電防止用作業靴を着用させる等労働者の身体、作業服等に帯電する静電気を除去するための措置を講じなければならない。

Article 286-2, paragraph (2)

A worker, when carrying out the work set forth in the preceding paragraph, must not carry out the work unless they conform to the requirements set forth in the same paragraph.

労働者は、前項の作業に従事するときは、同項に定めるところによらなければ、当該作業を行つてはならない。

Article 286-2, paragraph (3)

The provisions of the preceding two paragraphs do not apply when carrying out temporary work such as repair or alteration, and measures which are not likely to cause explosion or fire have been taken.

前二項の規定は、修理、変更等臨時の作業を行う場合において、爆発又は火災の危険が生ずるおそれのない措置を講ずるときは適用しない。

Article 287第二百八十七条

Removal of Static Electricity(静電気の除去)
Article 287, paragraph (1)

In using the following equipment, when there is a risk of explosion or fire due to static electricity, the employer must use a grounding connection, use a neutralizer, provide humidity, or use a neutralization apparatus which is unlikely to become an ignition source, and take other measures for eliminating static electricity:

事業者は、次の設備を使用する場合において、静電気による爆発又は火災が生ずるおそれのあるときは、接地、除電剤の使用、湿気の付与、点火源となるおそれのない除電装置の使用その他静電気を除去するための措置を講じなければならない。

Article 287, paragraph (1), item (i)

the equipment for pouring dangerous goods into a tank vehicle, a tank car, a drum, etc.;

危険物をタンク自動車、タンク車、ドラムかん等に注入する設備

Article 287, paragraph (1), item (ii)

the equipment for storing dangerous goods, such as a tank vehicle, a tank car, a drum, etc.;

危険物を収納するタンク自動車、タンク車、ドラムかん等の設備

Article 287, paragraph (1), item (iii)

the equipment for applying paints, adhesives, etc., containing inflammable substances;

引火性の物を含有する塗料、接着剤等を塗布する設備

Article 287, paragraph (1), item (iv)

drying equipment (drying rooms and dryers for heat-drying with a heat source substances other than gunpowder prescribed in Article 2, paragraph (1) of the Explosive Control Act (Act No. 149 of 1950); the same applies hereinafter) which heat-dry dangerous goods or materials to be dried that produce dangerous goods (hereinafter referred to as "drying equipment for dangerous goods"), or their attached equipment;

乾燥設備(熱源を用いて火薬類取締法(昭和二十五年法律第百四十九号)第二条第一項に規定する火薬類以外の物を加熱乾燥する乾燥室及び乾燥器をいう。以下同じ。)で、危険物又は危険物が発生する乾燥物を加熱乾燥するもの(以下「危険物乾燥設備」という。)又はその附属設備

Article 287, paragraph (1), item (v)

the equipment for spouting, sifting, etc., combustible powdery substances;

可燃性の粉状の物のスパウト移送、ふるい分け等を行なう設備

Article 287, paragraph (1), item (vi)

beyond the equipment set forth in the preceding items, chemical facilities (excluding piping) or their attached facilities.

前各号に掲げる設備のほか、化学設備(配管を除く。)又はその附属設備