Chapter V Prevention of Dangers Due to Electricity (Articles 344 to 354)
The law as Ministerial Order Partially Amending the Ordinance on Industrial Safety and Health (Ministry of Health, Labour and Welfare Order No. 68 of 2026) leaves it, with the words it changes marked.
The main text is read a page at a time: a chapter to a page, and a long chapter in runs of articles. The whole main text, and the supplementary provisions and appended tables this amendment changes. Those it leaves untouched are on the page for the text in force.
Article 344第三百四十四条
Extra High Voltage Live Line Work(特別高圧活線作業)
Article 344, paragraph (1)
In carrying out electric work such as inspecting, repairing and cleaning extra high voltage charged circuits or their supporting insulators, and when there is a risk of electric shock to the worker engaging in the work, the employer must take measures that fall under any of the following items:
to have the worker use live line work instruments. In this case, for the body, etc., the approach limit distance listed in the right column of the following Table must be maintained in accordance with the working voltage of charged circuit listed in the left column of the same Table; or
Working Voltage of Charged Electric Circuit (Unit: kV)
to have the worker use live line work equipments. In this case, the danger of electric shocks due to the body, etc., coming into contact or coming in proximity of an object having an electric potential different from the electric potential of the charged electric circuit or its supporting insulators handled by the worker must be eliminated.
A worker, when having been instructed to use a live line work instrument or live line work equipment by the employer in carrying out the work set forth in the preceding paragraph, must use the instrument or equipment.
Work in Proximity to Extra High Voltage Live Lines(特別高圧活線近接作業)
Article 345, paragraph (1)
In carrying out electric work such as inspecting, repairing, painting and cleaning an electric circuit or its supports (excluding supporting insulators for extra high voltage charged circuits), and when there is a risk of causing danger of electric shock to the worker engaging in the work due to coming in vicinity of an extra high voltage charged circuit, the employer must take measures that fall under any of the following items:
to have the worker use live line work equipment; or
労働者に活線作業用装置を使用させること。
Article 345, paragraph (1), item (ii)
to have body, etc., keep the approach limit distance to the charged circuit as prescribed in paragraph (1), item (i) of the preceding Article. In this case, to provide a sign, etc., at a readily visible location where the approach limit distance may be maintained, or to place a watcher and have the watcher watch the work.
A worker, when having been instructed to use live line work equipment by the employer in carrying out the work set forth in the preceding paragraph, must use it.
In carrying out the work of handling a low voltage charged circuit, such as inspecting or repairing the circuit, and when there is a risk of causing danger of electric shock to the worker engaging in the work, the employer must have the worker wear personal insulating protective equipment or use live line work instruments.
A worker, when having been instructed to wear personal insulating protective equipment or use live line work instruments by the employer in carrying out the work set forth in the preceding paragraph, must wear or use them, respectively.
Operations in Proximity to Low Voltage Live Lines(低圧活線近接作業)
Article 347, paragraph (1)
In carrying out electric work such as installing, inspecting, repairing, or painting an electrical circuit or its supports at a place in vicinity of a low voltage charged electric circuit, and when there is a risk of causing danger of electric shock to the worker engaging in the work due to coming into contact with the charged circuit, the employer must install an insulating device for the charged electrical circuit; provided, however, that this does not apply when having the worker engaging in the work wear personal insulating protective equipment, and the parts of the body, etc., other than those wearing the personal insulating protective equipment are unlikely to come into contact with the charged electrical circuit.
In the case referred to in the preceding paragraph, when having workers carry out work of installing or removing an insulating device, the employer must have the worker engaging in the work wear personal insulating protective equipment or use live line work instruments.
A worker, when having been instructed to install an insulating device, wear personal insulating protective equipment, or use live line work instruments by the employer in carrying out the work set forth in the preceding two paragraphs, must install, wear, or use them, respectively.
As regards personal insulating protective equipment, etc., listed in the following items, the employer must use the equipment whose type, materials and size are suitable for each purpose of use:
the personal insulating protective equipment set forth in Articles 341 through 343;
第三百四十一条から第三百四十三条までの絶縁用保護具
Article 348, paragraph (1), item (ii)
the insulating device set forth in Article 341 and Article 342;
第三百四十一条及び第三百四十二条の絶縁用防具
Article 348, paragraph (1), item (iii)
the live line work equipment set forth in Article 341 and Articles 343 through 345;
第三百四十一条及び第三百四十三条から第三百四十五条までの活線作業用装置
Article 348, paragraph (1), item (iv)
the live line work instruments set forth in Article 341, Article 343, and Article 344; and
第三百四十一条、第三百四十三条及び第三百四十四条の活線作業用器具
Article 348, paragraph (1), item (v)
the personal insulating protective equipment and the live line work instruments set forth in Article 346 and Article 347 and the insulating device set forth in Article 347.
第三百四十六条及び第三百四十七条の絶縁用保護具及び活線作業用器具並びに第三百四十七条の絶縁用防具
Article 348, paragraph (2)
As regards personal insulating protective equipment, live line work instruments and insulating device listed in item (v) of the preceding paragraph, which are used for a charged circuit of 750 V or less for direct current or of 300 V or less for alternating current, the employer must use those that have an insulating effect in accordance with the voltage of the charged circuit.
Prevention of Electric Shocks in Carrying Out the Work for Construction of Structures(工作物の建設等の作業を行なう場合の感電の防止)
Article 349, paragraph (1)
In carrying out the work such as constructing, dismantling, inspecting, repairing, and painting a structure or the work associated with them, or the work using a pile driver, pile drawer, mobile crane, etc., at a place in the vicinity of overhead wires or charged circuits of electric machine and appliance, when there is a risk of electric shocks to the worker engaging in the work due to the worker's body, etc., coming into contact or coming in the vicinity of the charged circuits during work or when passing through, the employer must take measures that fall under any of the following items:
to install an enclosure to prevent the danger of electric shock;
感電の危険を防止するための囲いを設けること。
Article 349, paragraph (1), item (iii)
to provide the charged circuit with insulating protective equipment; or
当該充電電路に絶縁用防護具を装着すること。
Article 349, paragraph (1), item (iv)
when taking measures falling under the preceding three items are extremely difficult, to place a watcher and have the watcher monitor the work.
前三号に該当する措置を講ずることが著しく困難なときは、監視人を置き、作業を監視させること。
Section 5 Management第五節 管理
Article 350第三百五十条
Supervision in Carrying Out Electric Work(電気工事の作業を行なう場合の作業指揮等)
Article 350, paragraph (1)
When carrying out the work set forth in Article 339, Article 341, paragraph (1), Article 342, paragraph (1), Article 344, paragraph (1), or Article 345, paragraph (1), the employer must make the period of carrying out the work, the content of the work, and the electric circuits handled, and the electric circuit system in vicinity of the electrical circuit known to the worker engaging in the work, as well as designate a supervisor of the work and have the supervisor carry out the following matters:
to make the method and procedures of the work known to the workers in advance, and directly supervise the work;
労働者にあらかじめ作業の方法及び順序を周知させ、かつ、作業を直接指揮すること。
Article 350, paragraph (1), item (ii)
when carrying out the work set forth in Article 345, paragraph (1) by taking the measures set forth in item (ii) of the same paragraph, to instruct the commencement of the work after having confirmed the installation of the sign, etc., or the placement of a watcher;
when carrying out work after opening the electrical circuit, to instruct the commencement of the work after having confirmed the power cut state of the electrical circuit, the switch used for the circuit opening being locked, indication of matters necessary to prohibit electric charge, placement of a watcher, and the state of fitting of the appliance for short circuit to ground after opening the electric circuit.
Periodical Self-inspection of Personal Insulating Protective Equipment(絶縁用保護具等の定期自主検査)
Article 351, paragraph (1)
As regards personal insulating protective equipment, etc., listed in each item of Article 348, paragraph (1) (for those listed in item (v) of the same paragraph, limited to those used for a charged circuit of low voltage exceeding 300 V in alternating current; hereinafter the same applies in this Article), the employer must carry out a self-inspection for the insulating performance, periodically once every period not exceeding six months; provided, however, that this does not apply to the non-use period of personal insulating protective equipment, etc., which is not used for a period exceeding six months.
As regards the personal insulating protective equipment, etc., set forth in the proviso of the preceding paragraph, the employer must carry out a self-inspection for the insulating performance before resuming the use.
When having found an abnormality in the personal insulating protective equipment, etc., as a result of the self-inspection set forth in paragraph (1) or (2), the employer must not use them unless having made repairs or taken other necessary measures.
When having carried out the self-inspection set forth in paragraph (1) or (2), the employer must record the following matters and preserve the record for three years:
the name of the person who has carried out the inspection; and
検査を実施した者の氏名
Article 351, paragraph (4), item (vi)
when measures such as repairs have been taken based on the result of the inspection, the details of the repairs.
検査の結果に基づいて補修等の措置を講じたときは、その内容
Article 351, paragraph (5)
The provisions of paragraph (1), paragraph (2) and the preceding paragraph apply mutatis mutandis to the self-inspection set forth in Article 45, paragraph (2) of the Act. In this case, the term "employer" in these provisions is deemed to be replaced with "individual business operator."
When having found an abnormality in the personal insulating protective equipment, etc. as a result of the self-inspection set forth in paragraph (1) or (2) as applied mutatis mutandis pursuant to the preceding paragraph, the individual business operator is to use them after repairs have been made or other necessary measures have been taken.
Inspection Before Using Electric Machine and Appliance(電気機械器具等の使用前点検等)
Article 352, paragraph (1)
When using electrical machinery and apparatus, etc. listed in the left column of the following table, the employer must, before commencing use for the day, inspect the inspection matters listed in the right column of the same table in accordance with the type of that electrical machinery and apparatus, etc., and when having found any abnormality, must immediately repair or replace it.
Type of Electrical Machinery and Apparatus, etc.
Inspection Matters
Holders for welding rods, etc. set forth in Article 331
Presence or absence of damage to the insulated protective portion and the connected portion of the cable for holders
Automatic voltage reducing devices for alternating current arc welding machines set forth in Article 332
Operating state
Earth-leakage circuit breakers for preventing electric shock set forth in Article 333, paragraph (1)
Motor-driven appliances set forth in Article 333 that are grounded by the method set forth in paragraph (2) of that Article
Presence or absence of abnormalities, such as disconnection of the ground wire or lifting of the grounding pole
Movable electric cables and the connecting tools attached to them set forth in Article 337
Presence or absence of damage to the covering or sheathing
Voltage detectors set forth in Article 339, paragraph (1), item (iii)
Voltage detection performance
Short-circuit grounding equipment set forth in Article 339, paragraph (1), item (iii)
Presence or absence of damage to the mounting fittings and grounding lead wires
Insulating protective equipment set forth in Articles 341 through 343
Presence or absence of damage such as cracks, splits and tears, and dryness
Insulating devices set forth in Articles 341 and 342
Live line work equipment set forth in Article 341 and Articles 343 through 345
Live line work instruments set forth in Articles 341, 343 and 344
Insulating protective equipment and live line work instruments set forth in Articles 346 and 347, and insulating devices set forth in Article 347
Insulating protective devices set forth in Article 349, item (iii) and Article 570, paragraph (1), item (vi)
Inspection of Enclosure of Electric Machine and Appliance(電気機械器具の囲い等の点検等)
Article 353, paragraph (1)
The employer must check for damage of the enclosure and insulating cover set forth in Article 329 more than once a month, and immediately make repairs when having found any abnormality.
The provisions of this Chapter do not apply to electric machines and appliances, wiring, or movable electric cables with voltage to ground of 50 V or less.
The day a law or an amendment starts to apply. It is often months or years after promulgation, so that people have time to prepare. The Ministry of Justice's English usually says a law "comes into force" or "comes into effect", and sometimes calls the day its "enforcement date". Its "enforcement" more often means the word's other sense, carrying a law out, as in an Order for Enforcement (施行令), the Cabinet Order (政令) that sets out the details for carrying out an Act.
The Ministry of Justice's English of this passage has a slip, so the English shown is this site's correction of it. The Ministry printed:
to have the worker use live line work instruments. In this case, for the body, etc., the approach limit distance listed in the right column of the following Table must be maintained in accordance with the working voltage of charged circuit listed in the left column of the same Table; or
Working Voltage of Charged Electric Circuit (Unit: kV) Minimum Allowable Proximity (Unit: cm)
22 or less 20
More than 22 and 33 or less 30
More than 33 and 66 or less 50
More than 66 and 77 or less 60
More than 77 and 110 or less 90
More than 110 and 154 or less 120
More than 154 and 187 or less 140
More 187 and 220 or less 160
More than 220 200
Japanese Law Translation, Ministry of Justice
Translates the law as amended by Order of the Ministry of Health, Labour and Welfare No. 185 of 2006 (平成十八年厚生労働省令第百八十五号)
The Ministry of Justice's English of this passage has a slip, so the English shown is this site's correction of it. The Ministry printed:
A worker, when having been instructed to use a live line work instrument or live line work equipment in carrying out the work set forth in the preceding paragraph, must use the instrument or equipment.
Japanese Law Translation, Ministry of Justice
Translates the law as amended by Order of the Ministry of Health, Labour and Welfare No. 185 of 2006 (平成十八年厚生労働省令第百八十五号)
The Ministry of Justice's English of this passage has a slip, so the English shown is this site's correction of it. The Ministry printed:
As regards personal insulating protective equipment, live line work instruments and insulating device listed in item (v) of the preceding paragraph, which are used for a charged circuit of 750 V or less for direct current or of 300 V or less for alternative current, the employer must use those that have an insulating effect in accordance with the voltage of the charged circuit.
Japanese Law Translation, Ministry of Justice
Translates the law as amended by Order of the Ministry of Health, Labour and Welfare No. 185 of 2006 (平成十八年厚生労働省令第百八十五号)
The Ministry of Justice's English of this passage has a slip, so the English shown is this site's correction of it. The Ministry printed:
In carrying out the work such as constructing, dismantling, inspecting, repairing, and painting a structure or the work associated with them, or the work using a pile driver, pile drawer, mobile crane, etc., at a place in the vicinity of overhead wires or charged circuits of electric machine and appliance, when there is a risk of electric shocks to the worker engaging in the work due to the worker' body, etc., coming into contact or coming in the vicinity of the charged circuits during work or when passing through, the employer must take measures that fall under any of the following items:
Japanese Law Translation, Ministry of Justice
Translates the law as amended by Order of the Ministry of Health, Labour and Welfare No. 185 of 2006 (平成十八年厚生労働省令第百八十五号)
The Ministry of Justice's English of this passage has a slip, so the English shown is this site's correction of it. The Ministry printed:
As regards personal insulating protective equipment, etc., listed in each item of Article 348, paragraph (1) (for those listed in item (v) of the same paragraph, limited to those used for an charged circuit of low voltage exceeding 300 V in alternative current; hereinafter the same applies in this Article), the employer must carry out a self-inspection for the insulating performance, periodically once every period not exceeding six months; provided, however, that this does not apply to the non-use period of personal insulating protective equipment, etc., which is not used for a period exceeding six months.
Japanese Law Translation, Ministry of Justice
Translates the law as amended by Order of the Ministry of Health, Labour and Welfare No. 185 of 2006 (平成十八年厚生労働省令第百八十五号)