# 労働安全衛生規則 / Ordinance on Industrial Safety and Health — 第六百一条 (Article 601)

This is the Markdown twin of https://japanlaw.org/en/industrial-safety-and-health-ordinance/art-601. Every law, and how to address a provision: https://japanlaw.org/llms.txt. The same laws as MCP tools (no sign-in): https://japanlaw.org/mcp.

- Law: 労働安全衛生規則 (Ordinance on Industrial Safety and Health), 昭和四十七年労働省令第三十二号
- English title "Ordinance on Industrial Safety and Health": Ministry of Justice translation
- Kind: MinisterialOrdinance — the distinction between 法律 (Act), 政令 (Cabinet Order), 省令 (Ministerial Order) and 条例 (local ordinance) decides who may issue it and what it may say.
- Provision: 第六百一条 (Article 601)（換気） — address `art-601`
- Text in force since: 2026-10-01
- URL (the page that opens at this provision): https://japanlaw.org/en/industrial-safety-and-health-ordinance/art-601
- e-Gov law ID: 347M50002000032 — never renamed. A permanent link, `/l/{lawId}/{address}` on this site, redirects to the page.
- Every provision below carries its address and its URL on the line under it.
- Japanese text: e-Gov 法令検索, Digital Agency (デジタル庁). English: as marked on each line below.

Only the Japanese as published by the government has legal effect; the text
below is a copy of it. Every English rendering below is a translation and
says which kind: the Ministry of Justice's translation, or this
site's machine translation, whose model and date the Sources list names.
They are never merged and never substituted for one another.

---

### 第六百一条（換気） — (Ventilation)
<sup>caption: Ministry of Justice translation — Japanese Law Translation Database System</sup>
<sup>art-601 · https://japanlaw.org/en/industrial-safety-and-health-ordinance/art-601</sup>

  **第一項**  事業者は、労働者を常時就業させる屋内作業場においては、窓その他の開口部の直接外気に向つて開放することができる部分の面積が、常時床面積の二十分の一以上になるようにしなければならない。ただし、換気が十分行なわれる性能を有する設備を設けたときは、この限りでない。
  <sup>art-601/par-1 · https://japanlaw.org/en/industrial-safety-and-health-ordinance/art-601/par-1</sup>
  In an indoor workshop where workers are regularly engaged in work, the employer must ensure that the total area for the part where the windows and other openings can be opened directly to the open air is one-twentieth or more of the floor area at all times; provided, however, that this does not apply when the indoor workshop is provided with facilities capable of providing sufficient ventilation.
  <sup>Ministry of Justice translation — Japanese Law Translation Database System</sup>

  **第二項**  事業者は、前条の屋内作業場の気温が十度以下であるときは、換気に際し、労働者を毎秒一メートル以上の気流にさらしてはならない。
  <sup>art-601/par-2 · https://japanlaw.org/en/industrial-safety-and-health-ordinance/art-601/par-2</sup>
  When the atmospheric temperature of the indoor workshop in the preceding Article is 10 degrees or lower, the employer must ensure that workers are not exposed to an air current of 1 m/sec or more in the process of ventilation.
  <sup>Ministry of Justice translation — Japanese Law Translation Database System</sup>

---

## Cites
- art-601/par-2: 前条 → 労働安全衛生規則 第六百条 (Article 600), art-600 — https://japanlaw.org/en/industrial-safety-and-health-ordinance/art-600

---

## Sources

- e-Gov 法令検索, Digital Agency (デジタル庁) — 労働安全衛生規則 — the text in force from 2026-10-01 (https://laws.e-gov.go.jp/law/347M50002000032/20261001_508M60000100116), retrieved 2026-11-13
- Japanese Law Translation Database System, Ministry of Justice (法務省) — Ordinance on Industrial Safety and Health — Ministry of Justice translation (https://www.japaneselawtranslation.go.jp/en/laws/view/3878/tb), retrieved 2026-11-13
- This site's parser, version 240 — 労働安全衛生規則 — structure, counts, cross-references and defined terms, computed 2026-11-13